| Supply voltage |
| Load voltage L+ |
| Rated value (DC) |
24 V |
| Power supply / Input / Input current |
| from load voltage L+ (without load), max. |
240 mA |
| from backplane bus 5 V DC, max. |
60 mA |
| Power losses |
| Power loss, typ. |
3 W |
| Analog outputs |
| Number of analog outputs |
4 |
| Cable length, shielded, max. |
200 m |
| Voltage output, short-circuit protection |
Yes |
| Voltage output, short-circuit current, max. |
25 mA |
| Current output, no-load voltage, max. |
18 V |
| Output ranges, voltage |
| 0 to 10 V |
Yes |
| 1 to 5 V |
Yes |
| -10 to +10 V |
Yes |
| Output ranges, current |
| 0 to 20 mA |
Yes |
| -20 to +20 mA |
Yes |
| 4 to 20 mA |
Yes |
| Load impedance (in rated range of output) |
| with voltage outputs, min. |
1 kΩ |
| with voltage outputs, capacitive load, max. |
1 µF |
| with current outputs, max. |
500 Ω |
| with current outputs, inductive load, max. |
10 mH |
| Analog value creation |
| Integrations and conversion time/ resolution per channel |
| Resolution with overrange (bit including sign), max. |
12 bit; +/-10 V, +/-20 mA, 4 to 20 mA, 1 to 5 V: 11 bits + sign; 0 to 10 V, 0 to 20 mA: 12 bits |
| Conversion time (per channel) |
0.8 ms |
| Settling time |
| for resistive load |
0.2 ms |
| for capacitive load |
3.3 ms |
| for inductive load |
0.5 ms; 0.5 ms (1 mH); 3.3 ms (10 mH) |
| Errors/accuracies |
| Operational limit in overall temperature range |
| Voltage, relative to output area |
+/- 0,5 % |
| Current, relative to output area |
+/- 0,6 % |
| Basic error limit (operational limit at 25 °C) |
| Voltage, relative to output area |
+/- 0,4 % |
| Current, relative to output area |
+/- 0,5 % |
| Interrupts/diagnostics/status information |
| Substitute values connectable |
Yes; Parameterizable |
| Alarms |
| Diagnostic alarm |
Yes; Parameterizable |
| Diagnoses |
| Diagnostic information readable |
Yes |
| Diagnostics |
Yes |
| Diagnostics indication LED |
| Group error SF (red) |
Yes |
| Galvanic isolation |
| Galvanic isolation analog outputs |
| between the channels and the backplane bus |
Yes |
| Isolation |
| Isolation checked with |
500 VDC |
| Connection method |
| required front connector |
20-pin(INCLUDE) |
| Dimensions and weight |
| Dimensions |
| Width |
40 mm |
| Height |
125 mm |
| Depth |
120 mm |